Characteristics of Indicators for Insulation Deterioration in 26 kV Generator Stator Windings
Soo-hoh Lee, Power Generation Laboratory, Korea Electric Power Corporation (KEPCO) Research Institute, Dae-jeon, South Korea
Hee-dong Kim, Power Generation Laboratory, Korea Electric Power Corporation (KEPCO) Research Institute, Dae-jeon, South Korea
Tae-sik Kong, Power Generation Laboratory, Korea Electric Power Corporation (KEPCO) Research Institute, Dae-jeon, South Korea
Received: Sep. 23, 2019;       Accepted: Oct. 16, 2019;       Published: Nov. 4, 2019
DOI: 10.11648/j.epes.20190806.11      View  12      Downloads  5
Abstract
This study conducted and analyzed the results of non-destructive tests (AC current, dissipation factor, and partial discharge tests) and a destructive test (overvoltage test) on 26 kV-generator stator windings with a ground fault. The target generator was a steam turbine generator in operation for over 30 years, and ground fault in windings occurred because of the rapid and instantaneous temperature rise in the copper conductor owing to the partial loss of generator cooling water. By comparing the non-destructive test data measured during the planned preventive maintenance period two years before the ground fault and the data gathered just after the ground fault, the study conducted an in-depth analysis of the effect of moisture on insulation diagnosis factors. If both the dissipation factor and capacitance data increased when compared to those of previously estimated values at same applied AC voltage level, it represented that the insulation materials absorbed moisture. Moreover, it was further developed that both of the dissipation factor and capacitance surge voltage were detected when the discharge started whereas the concerned surge voltage for AC current was detected when the discharge was proceeded in some extent. It is expected that a wider understanding of insulation diagnosis factors developed from this study will contribute not only to a more reliable diagnosis data analysis but also a stable power supply by preventing accidents in advance.
Keywords
Insulation, Stator Winding, Generator, AC Current, Dissipation Factor, Capacitance, Partial Discharge, Overvoltage
To cite this article
Soo-hoh Lee, Hee-dong Kim, Tae-sik Kong, Characteristics of Indicators for Insulation Deterioration in 26 kV Generator Stator Windings, American Journal of Electrical Power and Energy Systems. Vol. 8, No. 6, 2019, pp. 145-151. doi: 10.11648/j.epes.20190806.11
Copyright
Copyright © 2019 Authors retain the copyright of this article.
This article is an open access article distributed under the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0/) which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
Reference
[1]
H. D. Kim, “Analysis of Insulation Aging Mechanism in Generator Stator Windings,” J. Korean Inst. Electr. Electron. Mater. Eng., vol. 15, No. 2, pp. 119–126, 2002.
[2]
R. Morin, R. Bartnikas, and P. Menard, “A Three-Phase Multi-Stress Accelerated Electrical Aging Test Facility for Stator Bars,” IEEE Trans. on Electrical Conversion, vol. 15, No. 2, pp. 149–156, 2000.
[3]
H. D. Kim, T. S. Kong, S. K. Lee, B. S. Kim, and D. Y. Kim, “Analysis of Off-Line and On-Line Partial Discharge in High Voltage Motor Stator Windings,” J. Electr. Eng. Technol., vol. 10, No. 3, pp. 1086–31092, 2015.
[4]
H. D. Kim, “Analysis of Insulation Quality in Large Generator Stator Windings,” J. Electr. Eng. Technol., vol. 6, No. 2, pp. 384–390, 2011.
[5]
H. Zhu, V. Green, and D. Huynh, “Application of On-Line versus Off-Line PD Testing for Stator Insulation Monitoring,” Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, pp. 175–178, 1999.
[6]
T. S. Kong, H. D. Kim, T. S. Park, K. Y. Kim, and H. Y. Kim, “Analysis of Partial Discharge Patterns for Generator Stator Windings,” American J. Electrical Power Energy Sys., vol. 4, No. 2, pp. 17–22, 2015.
[7]
H. D. Kim, T. S. Kong, Y. H. Ju, and B. H. Kim, “Analysis of Insulation Quality in Large Generator Stator Windings,” Journal of Electrical Engineering & Technology, vol. 6, No. 2, pp. 384–390, 2011.
[8]
IEEE Standard, “IEEE Recommended Practice for Testing Insulation Resistance of Electric Machinery,” IEEE Std. 43, 2013.
[9]
Hazlee Illias, Teo Soon Yuan, Ab Halim Abu Bakar, Hazlie Mokhlis, George Chen, and Paul L. Lewin, “Partial Discharge Patterns in High Voltage Insulation,” IEEE International Conference on Power and Energy (PECon), pp. 750-755, 2012.
[10]
Wei Wang, Lin Yan, Tianzheng Wang, Hua Yu, Yu han, Xingting Liu, Na Zhang, and Na Wu, “PD Mechanism and Pattern Investigation for Stator Winding Insulation of HV Motors,” in Proceedings of 2016 IEEE International Conference on Mechatronics and Automation, Harbin, August 2016.
[11]
Claude Hudon and Mario Bélec, “Partial Discharge Signal Interpretation for Generator Diagnostics,” IEEE Trans. on Dielectrics and Electrical Insulation, vol. 12, No. 2, pp. 297–319, 2005.
[12]
H. D. Kim, T. S. Kong, T. S. Park, and T. H. Son, “Analysis of On-Line Partial Discharge Trend in Gas Turbine Generators”, International Journal of Energy and Power, vol. 3, no. 3, pp. 42-48, 2014.
[13]
H. D. Kim, T. S. Kong, S. K. Lee, B. S. Kim & D. Y. Kim “Analysis of off-line and on-line partial discharge in high voltage motor stator windings”, Journal of Electrical Engineering & Technology, Vol. 10, No. 3, pp. 1086–1092, 2015.
[14]
G. C. Stone, C. Chan, and H. G. Sedding, “On-line Partial Discharge Measurement in Hydrogen-Cooled Generators,” in 2016 IEEE Electrical Insulation Conference, Montréal, Canada, June 2016.
[15]
IEEE Standard, “IEEE Guide for Insulation Maintenance of Electric Machines,” IEEE Std. 56, 2016.
Browse journals by subject